Articulated Bellows
Significant challenges were encountered in the design of this 100m tall Ø600mm pipe riser, with the initial 1000kN pipe anchor loads (gravity + bellows thrust) exceeding the limits that could be supported by the existing concrete building core. A detailed analysis of pipe thermal effects, construction sequencing and design building movements enabled a reduction in the…